preloader
stuckeGROUP
SREN

SYMAP® ECO

Single Gen-set Control and Protection Device

Configuration in just a few steps. Ready for fast commissioning.

SYMAP® ECO is a single gen-set control and protection device that combines diesel generator control, generator protection and synchronization functions in one unit. It is designed for standard emergency generator applications in low-voltage systems and is based on predefined ECO Basic templates. Selecting the appropriate template and entering the basic parameters allows the configuration to be completed in just a few steps, significantly reducing commissioning time. The large graphical LC display and function keys provide intuitive operation, measurement overview and diagnostic functions.

Engineered for fast configuration

Thanks to ECO Basic templates and predefined inputs and outputs, configuration is completed in just a few steps. For standard applications, commissioning is typically reduced to 15 to 30 minutes.

1

Template selection

Three ECO Basic templates differ by the number of controlled circuit breakers, up to three. The template is selected in the ECO Parameter Tool, and the single-line diagram on the display automatically follows the selected configuration.

2

Predefined inputs and outputs

Standard signals and commands are already predefined: generator and mains breaker feedback, breaker open/close commands, synchronization signal (Sync ON), start signal, fuel valve and emergency stop. In addition, several freely programmable inputs and outputs remain available for project-specific requirements.

3

Basic parameters

Setup is menu-tree driven, either locally on the device or via a laptop. Parameters can be easily transferred to other SYMAP® ECO units with the same or similar configuration.

Low voltage. For low-voltage power systems; 400 V voltage measuring inputs.

Fast commissioning. Typically 15 to 30 minutes, through simple, intuitive setup.

14 inputs / 12 outputs. Mostly predefined, with a few free programmable.

Why SYMAP® ECO

A dedicated, standardized solution for reliable standby power from a single diesel genset, with no complex engineering and the shortest commissioning time.

Fast commissioning

ECO Basic templates and predefined inputs/outputs; a standard application is ready in 15 to 30 minutes.

All in one device

Genset control, generator protection and synchronization combined in a single device.

Reliability

Three microprocessors supervising each other (watchdog); all protection functions operate simultaneously.

Simple and secure

Local, password-protected setup and easy parameter transfer to other units; no remote programming.

SYMAP® ECO, ECG or BCG?

Same SYMAP platform and same quality. The difference is flexibility and scope: ECO is standardized and fast, ECG is flexible for more complex applications, and BCG covers the most complex systems and differential protection.

Same quality and reliability. All variants share the same SYMAP platform, three microprocessors with watchdog supervision and the same build and testing standard.
Feature
SYMAP® ECO
standard
this page
SYMAP® ECG
advanced / flexible
SYMAP® BCG
most complex / critical
Application Standard single genset More complex, multi-generator Most complex and critical
Voltage level Low400 V Low and medium Low and medium
Applications 3 preparedECO Basic 1/2/3 All applications All applications
Configuration Fixed (template) Flexible Flexible
Hardware and I/O Fixed14 DI / 12 DO, 2 AI, 2 AO Flexible, expandableCMA, up to 38 / 36 Flexible, expandableCMA, up to 38 / 36
Breaker control up to 3 up to 5 up to 5
Synchronization Generator to busbarone synchronizing unit, ANSI 25/A Generator to mains and generator to generatorparallel operation, with PMS Generator to mains and generator to generatorparallel operation, with PMS
Protection scope Standard genset set 40+ ANSI 40+ ANSI
Differential protection no Generator (87G)with CT-Diff group yesgenerator (87G) and transformer (87T); generator-transformer block via 87G+87T; REF (87N)
Power management (PMS) no Integrated PMSup to 14 generators Integrated PMSup to 14 generators
Communication Modbus RTU, CAN Flexible PROFIBUS, Modbus TCP, IEC 61850, IEC 60870-5-103
Required expertise Basic Advanced Advanced
Commissioning time 15 to 30 min Longer; depends on application Longer; complex engineering
Cost-effectiveness Economical dedicated solution for a standard genset Exceptionally cost-effective for anything non-standard Most cost-effective for the most complex and critical systems

For a standard single genset, ECO is the fastest and most cost-effective solution. As the application grows more complex (medium voltage, multiple generators, PMS, advanced protection), ECG becomes an exceptionally cost-effective choice. For the most complex and critical systems requiring differential protection, BCG is used.

SYMAP series (Y/BC)

Protection and control functions (ANSI)

  • ANSI 15, Matching device
  • ANSI 25/A, Automatic synchronising (check-sync)
  • ANSI 27 / 27B, Undervoltage (generator / bus)
  • ANSI 32, Overload
  • ANSI 46, Reverse phase current
  • ANSI 50 / 51, Overcurrent (instantaneous / time)
  • ANSI 59 / 59B, Overvoltage (generator / bus)
  • ANSI 81, Frequency protection
  • ANSI 94, Auxiliary voltage supervision
  • Reverse power; warning and shutdown levels

Genset control

  • Genset start-stop sequence; AUTO and MANUAL operating modes
  • ANSI 15 Matching Device for speed and voltage: converts Raise/Lower commands from regulation and synchronization into analog outputs or CAN commands to the governor, AVR or engine controller
  • Regulation via ±10 V / ±20 mA analog outputs or CAN-Bus communication to the engine control unit (ECU)
  • Generator and mains breaker control
  • Diesel engine control; protocols DEUTZ, VOLVO, SCANIA, J1939; MTU via CANBUS 2
  • Single-line display (busbar and breakers) on screen
  • Preferential trip management (priority-based load shedding)
  • Blackout management (start and recovery logic on supply loss)

Source transfer and synchronisation

  • Automatic mains failure (AMF): control of mains and generator breakers
  • overlap return to mains by back-synchronisation, with no power interruption (no-break)
  • over gap return to mains with a small interruption (open transition)
  • Supervision: alarm on back-synchronisation failure

Parallel operation with the mains is only momentary, during transfer; not for continuous grid-parallel operation.

Measurement and I/O

  • Generator currents and voltages (3 × CT, 3 × PT)
  • Bus / mains voltage (3 × PT, BUS2)
  • Generator and BUS2 frequency
  • Active, reactive and apparent power
  • Power factor per phase
  • Active and reactive energy counters in both directions
  • Operating hours, start/stop history and breaker operation counters
  • Voltage and current harmonics up to the 5th harmonic
  • Binary inputs (24 V DC) and binary outputs (including a "Sync ON" output); digital and analog outputs to switchboard controls

Communication

  • RS232 (front panel), programming and data output
  • RS485 MODBUS RTU to the supervisory/central system
  • CAN-Bus interface to the engine control unit (ECU)

Modbus RTU is available for data exchange with the supervisory/central system. The device has no remote programming: parameterization is done locally, and PC access is password-protected with operational timeout.

Recording and supervision

  • Recording unit: event history, detailed protection history, start/stop history
  • Permanent data store (independent of power supply)
  • Binary input supervision: wire break and short circuit; additional limits

Standards (type tests)

  • EMC: EN 61000-6-2 (immunity), EN 61000-6-4 (emission)
  • Vibration: IEC 60068-2-6
  • Measuring relays: IEC 60255
  • Degree of protection: IEC 60529

Technical data

Dimensions (cut-out)
192 × 192 mm
Weight
2.1 kg
Power supply
12 to 36 V DC
Power consumption
< 30 W
Boot time
3 s
Operating temperature
-20 to +70 °C
Protection (front plate)
IP54 (IEC 60529)
Protection (terminals)
IP10 (IEC 60529)
Binary I/O
14 DI / 12 DO
Analog inputs
2 (0/4-20 mA)
Analog outputs
±10 V / ±20 mA
Serial communication
Modbus RTU (RS485)
CAN
CANBUS 2 (engine)

Three microprocessors supervising each other (watchdog); all protection functions can operate simultaneously.

For more complex generator systems

SYMAP® ECO covers the standard single low-voltage diesel genset. For multi-generator plants, medium or high voltage systems, integrated Power Management System functions or more advanced generator protection, the appropriate SYMAP® variants are available.

SYMAP ECG and BCG

Multiple gensets, PMS and higher voltage levels

SYMAP® ECG and SYMAP® BCG are intended for more complex generator plants, multi-generator systems, medium- and high-voltage applications and integrated Power Management System (PMS) functions.

SYMAP series (Y/BC)
SYMAP G

Generator protection with an existing engine controller

SYMAP® G and SYMAP® BC are intended for applications where engine control is already handled by an existing engine controller, while SYMAP® provides generator protection, synchronization and connection functions.

SYMAP series (Y/BC)

Typical applications

Standby gensets

AMF / automatic source transfer

Auxiliary and pump stations

Industry and buildings

SYMAP® ECO is also suitable for replacing (modernizing) existing genset automation, within the applications listed above.

Who uses SYMAP® ECO

System integrators

Switchboard / panel builders

Shipbuilding and offshore

Industry and process plants

Data centers and critical facilities

Hospitals, airports, utilities

Need the technical datasheet?

For detailed specifications, setting ranges and configuration support, contact our team or request access to the documentation.